【Prev Products】 | 【Next Products】 |
![]() |
|
![]() ![]() ![]() ![]() ![]() |
1.Compact and suitable were space is limited
2.DIN rail mounting for easy installation
3.Load-breaking up to 8 times rated current making it ideal for motor isolation
4.Double-break with silver rivets-superior performance, reliability and long lasting
5.Highly visible red/yellow handle
6.Large padlockable red/yellow or grey/black handles
7.Comprehensive range, 16 to 32A models
8.High IP 66 rating
9.High breaking capacity with 12.5 mm contact air gap
10.Easy to install and operate
11.Easy snap-on fitting of auxiliary switches
Technical parameters |
Model |
FDIS-16 |
FDIS-25 |
FDIS-32 |
||
The following CNC according to IEC60947-3,the use of category DC21B |
||||||
Main parameters |
||||||
Rated insulation voltage |
Ui |
|
V |
1500 |
1500 |
1500 |
Rated heating current |
Ithe |
|
A |
16 |
25 |
32 |
Rated impulse withstand voltage |
Uimp |
|
V |
8000 |
8000 |
8000 |
Rated short-time withstand current(1s) |
Icw |
2,4 |
A |
800 |
900 |
1000 |
2H |
A |
1300 |
1500 |
1700 |
||
Rated short-circuit making capacity |
Icm |
2,4 |
A |
800 |
900 |
1000 |
2H |
A |
1300 |
1500 |
1700 |
||
Rated short-circuit current |
Icc |
|
A |
5000 |
5000 |
5000 |
Maximum fuse specifications |
gL(gG) |
|
A |
40 |
63 |
80 |
Mechanical life |
|
|
|
10000 |
10000 |
10000 |
DC poles |
|
|
|
2 or 4 |
||
Distance between contacts (pole-to-pole) |
|
|
mm |
8 |
||
Operating temperature |
|
|
℃ |
-25 ~+70 |
||
Storage temperature |
|
|
℃ |
-40 ~+70 |
||
Class of pollution |
|
|
|
2 |
||
Overvoltage category |
|
|
|
I to III |
||
IP level |
|
|
|
IP66 |